Bring high quality, safety and reliability to systems and operations
Meisonilan specializes in providing solutions for process control valves and shut-off valves to industries such as energy, chemical engineering, electric power, life sciences, and environmental protection. For many years, our automation technologies have been driving operational optimization. Leveraging our field-proven expertise, we provide support for your low-emission strategies.
Introduction

1. The electric V-ball valve is powered by AC220V, AC380V, or DC24V power supply voltage, and accepts current or voltage signals (4-20mA, 0-10mA, or 1-5VDC) from DCS, PLC systems, regulating instruments, operators, etc. to control operation. It adopts RC, 381R, PSQ, or HQ electronic angular stroke electric actuators, with internal servo operation and opening signal position feedback, position indication, manual operation and other functions. The structure design of mechatronics integration is strong in function, reliable in performance, simple in wiring, precise in control, small in size, light in weight, small in current resistance, large in flow coefficient, simple in structure, and good in sealing performance.


2. Angular stroke electronic electric actuator is the driving device of V-shaped valve. It is powered by power supply voltage and receives a unified standard signal (4-20mA, 0-10mA or 1-5VDC), which is converted into displacement corresponding to the input signal, changing the rotation angle of the valve core (any angle from 0-90o). Therefore, a certain input signal corresponds to a certain angle, achieving proportional action. Two position switch type accepts power from AC220V or AC380V, and achieves switch action through motor forward and reverse rotation, while simultaneously outputting valve position indication signals.


Technical Parameter

Main performance and technical parameters of the actuator

Model Output torque N.m Action time S/90° Power (W) Model Output torque N.m Action time S/90° Power (W) Model Output torque N.m Action time S/90° Power (W)
HL-5 50 10/30 10W/F 381RSA-02 20 8.5 50 PSQ51 50 23 24.2
HL-10 100 15/30 23W/F 381RSA-05 50 17 PSQ66 65 32 24.2
HL-20 200 10/15/30 40W/F 381RSB-10 100 18 150 PSQ76 75 60 25.3
HL-40 400 10/15/30 80W/F 381RSB-20 200 36 PSQ102 100 32 62.1
HL-50 500 10/15/30 90W/F 381RSC-30 300 24 220 PSQ202 200 28 93.0
HL-100 1000 50 100W/F 381RSC-50 500 42 PSQ502 500 43 120
HL-200 2000 100 100W/F 381RSC-60 600 48 PSQ702 700 43 120




381RSD-100 1000 30 300 PSQ1202 1200 31/37 500




381RSD-150 1500 38 PSQ2002 2000 93/112 500




381RSD-200 2000 46



(Use shielded wire for signal line) Protection level: IP65. With crank manual operation. Power supply: AC220V/AC380V/DC24V (Use shielded wire for signal line) Protection level: IP55. Explosion-proof mark: ExdⅡBT4. With crank manual operation. The performance of the explosion-proof (381RX) type is the same as above. Power supply voltage: AC220V (Use shielded wire for signal line) Protection level: IP65. With handwheel operation. Power supply voltage: AC220V


Main part materials and applicable temperature

Material code C (WCB) P (304) R (316)
Main parts Valve body WCB ZG1Cr18Ni9Ti ZG1Cr18Ni12Mo2Ti
Ball 2Cr13, (304) 0Cr18Ni9Ti 0Cr18Ni12Mo2Ti
Valve stem 2Cr13 0Cr18Ni9Ti 0Cr18Ni12Mo2Ti
Sealing ring Reinforced polytetrafluoroethylene, para-polyphenylene, hard alloy steel
Packing Polytetrafluoroethylene, flexible graphite
Applicable working conditions Applicable medium Water, steam, oil products Nitric acid and alkalis Acetic acid
Applicable temperature -28°C - 500°C


Allowable pressure difference (MPa)

Nominal diameter 25 32 40 50 65 80 100 125 150 200 250 300
Air supply 0.5MPa 5.9 5.4 4.8 4.5 4.3 3.6 2.8 2.0 1.4 1.3 1.1 0.8


Product technical parameters and performance indicators

Nominal diameter D (mm) 25 32 40 50 65 80 100 125 150 200 250 300
Rated flow coefficient Cv 32 43 78 90 160 250 360 610 1120 1850 2950 3700
Nominal pressure PN (MPa) 1.6, 2.5, 4.0, 6.4
Flow characteristic Approximately equal percentage (see typical curve diagram), linearity, quick-opening characteristic
Valve plate rotation angle (degrees) 0° - 90°
Allowable leakage level Soft seal: Zero leakage. Hard seal: ≤10 - 5 rated flow coefficient
Actuator model HL, 3810R, PSQ, HQ or QB type
Action form On - off type, intelligent adjustment type, (Explosion - proof type)
Power supply voltage AC220V 50Hz or AC380V 50Hz
Adjustment type Input signal 0 - 10mA, 4 - 10mA, 1 - 5VDC
Output signal 0 - 10mA, 4 - 10mA, 1 - 5VDC
Basic error ≤±1.5%
Hysteresis ≤1.5%
Dead zone ≤0.3%
Adjustable ratio 250:1 300:1
On - off type Power supply voltage AC220V/AC380V/AC110V
Feedback signal Active contact signal, passive contact signal (optional)


Installation dimension table of pneumatic V - type ball valve

Nominal diameter Dimensions (mm)
Wafer type Flanged type
D L L1 D D1 D2 L Z - D
25 64 50 25 115 85 65 102 4 - 14
40 82 60 25 135 110 85 114 4 - 18
50 100 75 32 145 125 100 124 4 - 18
65 120 85 38 160 145 120 145 4 - 18
80 131 100 45 180 160 135 165 8 - 18
100 158 115 50 195 180 155 194 8 - 18
125 180 135 55 215 210 185 213 8 - 18
150 216 160 65 245 240 210 229 8 - 23
200 268 200 80 280 295 265 243 12 - 23
Valve Installation & Maintenance
Valve Installation:
(1) Before installation, check that the product model, tag number, and specifications match the requirements. Inspect the entire valve for missing or loose parts.
(2) Prior to installation, clean the pipeline. Ensure there is sufficient straight pipe section at the valve inlet and install a filter. When connecting the valve body to the pipeline flanges, ensure coaxiality.
(3) Thoroughly clean the pipeline before installing the valve.
(4) The installation site should ensure the safety of personnel and equipment, facilitating operation, disassembly, and maintenance.
(5) The valve should be installed vertically upright on horizontal pipelines. If necessary, it can be installed at an angle, but horizontal installation should be avoided. For occasions with heavy valve weight or vibration, use a support frame.
(6) The medium flow direction must align with the arrow on the valve body. The air supply should be dry and oil-free. The valve should be used in environments with temperatures ranging from -20℃ to 55℃.

Valve Maintenance:
(1) Cleaning the Valve: For general media, cleaning with water is sufficient. For media harmful to health, first understand their properties and then select an appropriate cleaning method.
(2) Disassembly: Remove rust from exposed rusted parts first. Before derusting, protect the machined surfaces of precision parts such as the valve seat, valve plug, valve stem, and push rod. Use special tools when disassembling the valve seat.
(3) Valve Seat: Minor rust or wear on the sealing surface can be repaired by machining. If damage is severe, replace the seat. However, both repaired and replaced hard sealing surfaces must be lapped.
(4) Valve Stem: If the surface is damaged, it must be replaced.
(5) Damage to Push Rod, Guide, and Sealing Surfaces: Reverse-acting actuators must be replaced; direct-acting actuators can be reused after proper repair.
(6) Compression Spring: If there are cracks or other defects affecting strength, replace it immediately.
(7) Wear Parts: Packing, gaskets, and O-rings must be replaced entirely during each maintenance. Check the valve plug and diaphragm for cracks, aging, or corrosion that may cause future failures. Decide whether to replace them based on inspection results, but the diaphragm service life should not exceed 2-3 years.
(8) When reassembling the valve, ensure alignment. Tighten bolts diagonally and lubricate sliding parts. After reassembly, debug the valve according to the factory test items and methods. During this period, accurately adjust the packing compression force and the valve plug closing position.
Ordering Instructions
When placing an order, please fill in the Specification Sheet or specify the following information:
  1. If the model has not been selected before ordering, please provide us with the operating parameters:
    (1) Nominal diameter DN (mm);
    (2) Nominal pressure (MPa or bar);
    (3) Fluid properties (including medium temperature, viscosity, or acidity/alkalinity);
    (4) Pressure before and after the valve (pressure differential);
    (5) Requirements for flow characteristics;
    (6) Materials of valve body and valve core;
    (7) Connection type;
    (8) Driving method (provide air supply pressure, driving voltage);
    (9) Supporting accessories (for pneumatic valves, it is recommended that users install an air filter triplet and a 2-position 5-way solenoid valve);
    (10) On-site working conditions.
  2. If the product model of our company has been selected by the design unit, please order directly from our production department according to the model;
  3. When the application occasion is very important or the pipeline is relatively complex, please provide the design drawings and detailed parameters as much as possible, and our experts will review and check them for you.
Upload order instructions Submit Now
Request Quote
Get your exclusive quotation
  • Your phone number
  • Your email
  • Your name
  • Your company
  • Selected product
  • Request details

National Unified Service Hotline
(086 )0512-68126111
Email: sales@meisonilan.com
Address: No. 2588, Tian'e Dang Road, Hengjing, Wuzhong District, Suzhou City
【Scan WeChat】
Copyright © 2021 Meisonilan Valves (Suzhou) Co., Ltd. All Rights Reserved.
Privacy Policy